Overvoltage (electrical engineering)

from Wikipedia, the free encyclopedia

Overvoltage is an electrical voltage in electrical systems that exceeds the tolerance range of their nominal voltage .

Overvoltages lead to a malfunction or failure if they destroy components or parts of the system. Overvoltages can occur symmetrically , that is, between the two supply lines, or asymmetrically  - both supply lines carry overvoltage to earth.

causes

Causes for long-term overvoltages in the range of seconds to hours can be:

Causes of transient overvoltages can be:

Also NEMP and solar activity on Earth caused magnetic storms cause power surges.

Transient overvoltages from neighboring sources of interference can also couple capacitively (due to influence) or inductively into supply or signal lines and can also be caused by strong radio waves .

consequences

Consequences of transient (short-term) overvoltages
Consequences of prolonged surges

remedy

Long-term overvoltages in the supply network can only be prevented by the consumer with a network regulator . Such network regulators are, however, common and useful only for individual, particularly sensitive and expensive electrical consumers .

Transient overvoltages can be kept away from endangered components with surge arresters (see also surge protection ):

On the mains voltage side, insulation, air and creepage distances are still oversized in order to avoid electrical breakdown in the event of high voltage pulses .

Electronic components as well as electrical end devices for mains voltage operation are tested as part of the electromagnetic compatibility test with regard to their immunity to transient overvoltages of 500 to 4000 volts (sometimes up to 15,000 volts) and specified accordingly or, in the case of end devices, certified according to standards for industrial, medical or home use . This includes:

  • ESD test (pulse rise time approx. 1 ns) according to the human body model or the machine model
  • Burst test (pulse trains with 5 ns rise time and 50 ns duration)
  • Surge test (impulses with 1.2 / 50 µs or 8/20 µs rise / fall time)

Overvoltage categories

The overvoltage category according to DIN EN 60664-1 VDE 0110-1 describes the overvoltage resistance of electrical equipment (electrical installation, measuring device, electrical device, power supply, etc.). There are four categories, denoted by Roman numerals from I (lowest) to IV (highest). Since the power grid itself spreads overvoltage events, the closer the equipment is to the distribution network, the higher the requirements. In detail, the classes mean:

  • Category I: Devices beyond a mains transformer (mostly low voltage consumers); Rated impulse voltage 1500 V
  • Category II: Devices with IEC plugs , typical household devices , hand-held electrical devices ; Rated surge voltage 2500 V
  • Category III: devices connected directly to the network (permanently installed); Rated impulse voltage 4000 V
  • Category IV: Equipment directly at the point of supply in the building; Rated impulse voltage 6000 V

The surge voltage resistance is ensured by appropriate air and creepage distances, the dielectric strength of interference suppression capacitors or the group and type of insulation material .

Individual evidence

  1. VDE Electromagnetic Compatibility , accessed on June 22, 2016.
  2. DIRECTIVE 2014/30 / EU OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of February 26, 2014 on the harmonization of the legal provisions of the member states relating to electromagnetic compatibility (new version)